Residential central air conditioning systems that need to cool and 
            dehumidify uses a condenser, evaporator coil, and refrigerant piping 
            to operate. The means of moving the air might differ (furnace, air 
            handler, etc.), but the principal is the same for all split systems. 
            Freon is compressed and run through a series of tubes to remove as 
            much heat as possible, then piped to an evaporator coil as a warm 
            liquid. Expansion of the compressed liquid causes it to cool, and as 
            the air passes over the coil, heat is extracted. The cool liquid 
            becomes a cool gas as it gathers heat from the air, and is drawn 
            back to the compressor to start the procedure again. As the air 
            passes over the evaporator coil and cools, moisture in the air 
            condenses and drains off as condensate.
MRW Mechanical Information Center
CENTRAL AIR CONDITIONING
                  Some hybrid and geothermal systems use cold water instead of 
                  freon until the temperature gets to a certain point, but the 
                  majority of systems use freon for the entire cooling cycle. 
                  In arid climates when dehumidification is not needed, only 
                  cooling, evaporative air conditioning is practical and 
                  economical.
                  Evaporative systems can be as simple as a pond of water on a 
                  flat roof, or more involved with the use of air handling 
                  equipment and special fabrics. By running water down loose 
                  material that is suspended and blowing air through the wet 
                  fabric, the evaporation of water will lower the air 
                  temperature and raise the humidity. The water that does not 
                  evaporate will be cooled down enough to contain in a vessel 
                  and become a secondary source of cooling by moving air over 
                  the vessel to create air conditioning.
                  Split systems that use freon are of the same design, no matter 
                  what the source of air handling equipment used(furnace, heat 
                  pump, hydro-air, etc.).
                             
            Basic troubleshooting for split systems: 
              First make sure that the thermostat is set lower than the actual 
              room temperature. The selector switch must be on "cool". If the 
              thermostat is programmable, be certain it has fresh batteries. 
              Check for power by moving the fan switch from "auto" to "on". If 
              the blower runs, there is power. If nothing happens, a control is 
              burned out or power is disconnected. If the system uses a furnace 
              for heat, check that the emergency switch is on. If you are 
              familiar with the fuse or circuit breaker panel, check for blown 
              fuses or tripped breakers. Correct the problem one time only. If 
              it repeats, call for service. 
              With the selector switch on cool and the fan switch on auto, move 
              the thermostat well below room temp. If the blower runs but the 
              condenser(outdoor unit) does not, check the circuit breaker panel. 
              If the breaker is on, examine the condenser. Some have a high 
              pressure cut out. It is a button sticking out of the cabinet, 
              usually near the refrigerant lines. Push it in as far as it will 
              go to reset it. 
              If both units are running and no cooling is taking place, touch 
              the larger of the two copper lines exiting the condenser. If it if 
              warm, the system is out of freon or the compressor is down. If the 
              line is frozen or iced over, the is an air flow problem inside, 
              such as clogged filter or too many registers closed or an object 
              covering the return duct. A low freon charge will also cause a 
              freeze-up. Shut the system down and let it thaw out completely. If 
              it freezes up again, call for service. 
              If the unit is in the basement and has a condensate pump, the 
              control wire for the condenser might be wired through a safety 
              switch on the pump. Check to see if the pump is plugged in and 
              operable. 
              If the unit is in the attic, there could be a float switch in the 
              air handler or in the safety pan that will shut the condenser off 
              if the drain is clogged. Water around the unit is evidence of 
              trouble. Call for service.